Two ways storage
earns its keep.
Two factories with identical consumption can need opposite storage strategies. The difference is in the tariff, not the equipment.
Mechanism one: demand charges
Many industrial tariffs charge for the highest demand recorded in a billing period, often with a rolling 15- or 30-minute window. Storage earns by clipping those peaks. The required power rating is set by the peak you want to shave; runtime only needs to cover the peak's duration. Dispatch must react fast and reliably every month, because one unclipped peak can erase a year of savings.
Mechanism two: time-of-use spread
Where the tariff is dominated by a price difference between cheap and expensive hours, storage earns by charging low and discharging high. Here usable energy capacity matters more than power, and the strategy depends on predictable daily cycles. A system optimised for arbitrage may be poorly suited to demand clipping, and vice versa.
Read your bill before you size
Look at the largest demand line and the energy-price structure. If the demand charge is a substantial share of the bill, prioritise peak shaving. If the spread between off-peak and peak energy prices is wide and stable, arbitrage will dominate. Many markets offer both, in which case a controller that can switch strategies is worth paying for.
Why dispatch control matters
The cabinet is only half the system. A controller that reads the tariff, the load and the state of charge — and dispatches accordingly — determines whether the asset earns. Ask how the strategy is configured, whether it can be updated remotely when tariffs change, and what happens during a grid outage.
Frequently asked questions
- Can one system do both?
Yes, with a controller that supports multiple modes. The sizing is a compromise, so optimise for the mechanism that dominates your bill.
- How fast must peak shaving respond?
Within seconds. A peak that lasts a few minutes can still set the monthly demand charge if the system reacts late.
- Do tariffs change the calculation over time?
Yes. Choose a controller that can be reconfigured remotely so the strategy can be updated without a site visit.
Not sure which applies to you?
Send a copy of your electricity bill with the tariff structure. We will tell you which mechanism dominates and what configuration it implies.